Invertek ODE-3-440460-3F42

Optidrive E3                              Vector or Volts / Hertz Control

30 HP,   440 Volts AC,   3 Phase In,   3 Phase Out,   IP20 (Nema1)

Brake Transistor                           EMC Filter                      

More details

Invertek ODE-3-440460-3F42


$1,586.48

Availability: Please call for availability, 1-800-966-2585


Notify me when available

Optidrive E3

 

AC Volts / Hz Variable Frequency Drive

30 Horsepower

Input: 380-480 Volts Three Phase, 51.9 Amps Nominal

Output: 380-480 Volts Three Phase, 46 Amps Nominal

Recommended Fuse / MCB Size (B-curve):  Non-UL - 63 Amps   UL - 70 Amps

Brake Transistor Fitted, Recommended Brake Resistance: 22 Ohms

IP20 (Nema 1)

Frame Size 4 - 16.54 in x 6.73 in x 8.35 in ( L x W x D ), 20.1 Lbs

Internal EMC Filter


 

 

Compact, Reliable and Easy to Use

Simply power on and Optidrive E3 is up and running, providing precise motor control and energy savings using the factory settings.

 

Sensorless Vector Control for all Motor Types

Precise and reliable control for IE2, IE3 & IE4 motors.

  • Induction Motors (IM)
  • Permanent Magnet Motors (PM)
  • Brushless DC Motors (BLDC)
  • Synchronous Reluctance Motors (SynRM)

Simple Commissioning

14 parameter basic setup. Default settings suitable for most applications. Contactor style connection for simple wiring.

Intuitive Keypad Control

Precise digital control at the touch of a button.

Application Macros

Switch between Industrial, Pump & Fan modes to optimise Optidrive E3 for your application.

Internal Category C1 EMC Filter

An internal filter in every Optidrive E3 saves cost and time for installation.

Cat C1 according to EN61800-3:2004



 

Optidrive E3 Features

Innovative technology, reliability, robustness and ease of use in a range of compact IP20 & IP66 enclosures.

Sensorless Vector Control for all Motor Types

Precise and reliable control for IE2, IE3 & IE4 motors.

  • Induction Motors (IM)
  • Permanent Magnet Motors (PM)
  • Brushless DC Motors (BLDC)
  • Synchronous Reluctance Motors (SynRM)

Internal Category C1 EMC Filter

An internal filter in every Optidrive E3 saves cost and time for installation.

Cat C1 according to EN61800-3:2004

 

 

Application Macros

Switch modes at the touch of a button to
optimise Optidrive E3 for your application


Industrial Mode

Industrial mode optimises Optidrive E3 for load characteristics of typical industrial applications.

Applications include:

  • Conveyors
  • Mixers
  • Treadmills

Pump Mode

Pump mode makes energy efficient pump control easier than ever.

Applications include:

  • Dosing Pumps
  • Borehole Pumps
  • Transfer Pumps
  • Swimming Pools
  • Spas
  • Fountains

Fan Mode

Fan mode (inc. fire operation) makes air handling a breeze, ideal for simple HVAC systems.

Applications include:

  • Air Handling Units
  • Ventilation Fans
  • Circulating Fans
  • Air Curtains
  • Kitchen Extract



 

 

Specifications

 

 Output ratings Typical Efficiency > 98%
  Overload Capacity 150% for 60 secs
175% for 2 secs
  Frequency 0…500Hz, 0.1Hz resolution
Input Ratings Supply Frequency 48 - 62Hz
  Displacement Power Factor > 0.98
  Phase Imbalance 3% Maximum allowed
  Power Cycles 120 per hour maximum, evenly spaced

Ambient Conditions

Temperature Storage: -40 to 60°C
Operating: -10 to 50°C
  Altitude Up to 1000m ASL without derating
Up to 2000m maximum UL approved
Up to 4000m maximum (non UL)
  Humidity 95% Max, non condensing 
   Vibration Conforms to EN61800-5-1 
  Ingress Protection IP20 (Nema 1)
Programming Keypad Built-in keypad as standard
Optional remote mountable keypad
  PC OptiTools Studio
  Display 7 Segment LED
Control Specification Control Method  Sensorless Vector Speed Control
PM Vector Control
BLDC Control
Synchronous Reluctance
  PWM Frequency 4 – 32kHz Effective
  Stopping Mode Ramp to stop: User Adjustable 0.1 – 600 secs
Coast to stop
  Braking Motor Flux Braking
Built-in braking transistor (not frame size 1)
  Skip Frequency   Single point, user adjustable 
  Frequency setpoint control 0…10 VDC
0…20mA
4…20mA
Motorised Potentiometer (Keypad)
Modbus RTU
CANopen
I/O Specification Power Supply 24 Volt DC, 100mA, Short Circuit Protected
10 Volt DC, 5mA for Potentiometer
  4 Total
  2 Digital
  2 Analog / Digital Selectable
4 Total
  2 Digital
  2 Analog / Digital Selectable
  Digital Inputs 8 – 30 Volt DC, internal or external supply
Response time < 4ms
  Analog Inputs Resolution: 12 bits
Response time: < 4ms
Accuracy: ± 2% full scale
Parameter adjustable scaling and offset
  Programmable Outputs 2 Total
  1 Analog / Digital
  1 Relay
  Relay Outputs Maximum Voltage: 250 VAC, 30 VDC
Switching Current Capacity : 6A AC, 5A DC
  Analog Outputs 0 to 10 Volt
Application Features Fire Mode Bidirectional
Selectable Speed Setpoint (Fixed / PI / Analog / Fieldbus)
  PI Control Internal PI Controller
Standby / Sleep Function
 Maintenance & Diagnostics Fault Memory Last 4 Trips stored with time stamp
  Data Logging Logging of data prior to trip for diagnostic purposes:
  Output Current
  Drive Temperature
  DC Bus Voltage
 Bus communication Modbus RTU  9.6–115.2 kbps selectable 
   CANOpen 125–1000 kbps 
 Compliance with Standards  Low Voltage Directive  Adjustable speed electrical power drive systems.
EMC requirements
  EMC Directive   2004/108/EC
Cat C1 according to EN61800-3:2004
   Machinery Directive 2006/42/EC 
  Conformance  CE, UL, RCM 







 





 



  • Motor Power: 30 Horsepower
  • Input Voltage: 380-480 VAC 3 Phase
  • Output Voltage: 380-480 VAC 3 Phase
  • Control Type: Vector
  • IP Rating: IP20
  • Electro-Magnetic Shield: EMC Filter Fitted
  • Braking Transistor: Internal Transistor
  • Disconnect Switch: No Disconnect Switch
  • UL Approval: Yes
  • Minimum Fuse Size 63 Amps
  • Output Amperage: 46 Amps
  • Input Amperage 51.9 Amps