Invertek ODP-2-24010-3HF4*
Optidrive P2 Sensorless Vector Control
1.0 HP, 440 Volt AC, 3 Phase In, 3 Phase Out, IP66 (Nema4X)
EMC Filter & Brake Transistor * = Disconnect Switch Optional
Optidrive P2 Sensorless Vector Control
1.0 HP, 440 Volt AC, 3 Phase In, 3 Phase Out, IP66 (Nema4X)
EMC Filter & Brake Transistor * = Disconnect Switch Optional
Optidrive P2
AC Vector Variable Frequency Drive
1.0 Horsepower
380-480 Volt Three Phase Input
380-480 Volt Three Phase Output
Internal EMC Filter
Brake Transistor Fitted
IP66 (Nema 4X)
Frame Size 2 - 8.7 in x 4.4 in x 7.3 in ( L x W x D ), 3.97 Lbs
Optional:
Disconnect Switch
World Leading Motor Control
The all new Optidrive P2 provides world leading control for both standard induction motors and permanent magnet motors.
Open loop vector control of standard induction motors provides up to 200% torque from zero speed
Open and closed loop control of the latest generation of high efficiency PM motors
Closed loop encoder feedback capability for standard induction motors
Extensive I/O and communications interface capabilities ensure the drive can be integrated quickly and efficiently into a wide variety of control systems.
A simple parameter structure and carefully selected factory settings ensure fast and easy commissioning.
Specifications
Input Ratings |
Supply Voltage |
400V: 380 – 480V ± 10% |
Supply Frequency |
48 – 62Hz |
|
Phase Imbalance |
3% maximum |
|
Inrush Current |
< rated current |
|
Power Cycles |
120/hour max, evenly spaced |
|
Output Ratings |
Output Power |
400V 3 Phase Input: 0.75 – 160kW |
Overload Capacity |
150% for 60 seconds, 200% for 2 seconds |
|
Output Frequency |
Up to 500Hz |
|
Ambient Conditions |
Temperature |
Storage: |
Altitude |
1000m with no derating |
|
Humidity |
95% max, non-condensing |
|
Enclosure |
Ingress protection |
IP66 optional |
Programming |
Keypad |
Yes |
PC |
Yes |
|
Preset speeds |
8 user adjustable |
|
PID control |
Internal |
|
Spin start |
Yes |
|
Acceleration |
0 – 3000 secs, 0.1 resolution |
|
Deceleration |
1st Ramp: 0 – 3000 secs, 0.1 resolution |
|
Performance |
Speed regulation |
Open Loop: ± 20% of motor slip |
Torque control |
0 – 200% of motor rated torque |
|
Control Specification |
Control method |
V/F Voltage Vector |
Stopping mode |
Coast Stop |
|
Skip frequency |
Single point, user adjustable |
|
Setpoint control |
0 – 10V |
|
Setpoint control |
PROFIBUS |
|
I/O Specification |
Digital inputs |
10 – 30V DC, internal or external supply, NPN |
Power supply |
24V DC, 100mA, Short Circuit protected |
|
Analog inputs |
;10 – 10V DC |
|
Analog outputs |
0 – 10V |
|
Relay outputs |
Maximum Voltage : 250V AC, 30V DC |